Why is Load Rejection Performed?
Since the power of the power plant or
generator used as an energy source is insufficient for the loads to be
activated, it is necessary to install a load cycling-rejection system in order
to prevent the power plant from overloading or operating at low load.
Two different operating scenarios arise
here;
1- Static Load cycling - rejection system
Preventing the system from overloading by
deactivating a certain fixed load. This is, for example, the case where a block
load is deactivated so that the source (usually the generator) that is
activated in the event of a power failure or a power plant that falls into the
islanding are not overloaded. This can be easily implemented with a simple
automation. This deactivated load is permanently deactivated until the
transformer/network, which is the main source, is back.
This can also work the other way around.
For example, it can also be in the form of commissioning of a particular load
bank so that the low-load backup source (usually the generator) does not fail
due to low load operation in the long run.
2-Dynamic
Load cycling - rejection system
The load cycling-rejection sequence is
the continuous controlled deactivation or activation of more than one point
that can be adjusted by an automation system to prevent overloading of back-up
power supply or a Co-Gen system that goes into islanding. However, in order to
prevent the continuous de-energization and return of the load, the number of
deactivation or activation can also be limited.
It is also possible to divide such
systems into two.
2a- Fast load rejection
If the overload capacity of the source
is limited, it is the state of switching off the load within a maximum of 100
ms by controlling the load increase continuously. In such fast systems, load control
must be done with a transducer that can measure the changing load
information every 20-50 ms and give it analogously (4-20 mA or 0-10V).In
addition, the analog output of this transducer must be connected to an RTU system
that updates the status information every 1 ms. However, in this way, the
load(s) can be disabled within 100 ms max, taking into account the breaker
opening time, which is around 60 ms.
Our company can make all kinds of load rejecting
systems from generators to power plants with its engineering professional staff
of Fesis Automation. In fact, it is possible to easily manage the load
rejecting scenario with the EMS module of the HYPERLINK
"https://www.sge.com.tr/kategori-zenon-scada-159.html" o
"zenon" t "_blank" xenon scada,
which of we are distributors.
Address: Bayındır, 333. Sk. 15/A, 07030 Muratpaşa/Antalya
Phone: (0242) 237 52 37
gsm: (0242) 237 52 37
Email: info@fesis.com.tr